Three Phase Sewage Water Pump Controller Specialized In Sewage Lifting
| Product Details: Place of Origin:China Brand Name:LEADING Certification:CE Model Number:L932-S Payment & Shipping Terms: Minimum Order Quantity:1 set Price:Negotiable PackagingDetails:Carton Delivery Time:30-35 days Payment Terms:D/A, L/C, D/A, D/P, T/T Supply Ability:5000 Pcs / Each Month |
Detailed Product Description
Phase: | Three Phase | Pump Controlled Quantity: | Two Pumps |
Enclosure Protection Grade: | IP54 | Install Position: | Wall Mounting |
Displaying : | LCD Display | Liquid Level Transfer Distance: | ≤1000m |
General Description
L932-S pump controller is a compact wall mounted unit which will manage the operation of a Duty & Standby pump motor combination applicable for waste water management.
Comparison From Our Digital Controller To Traditional Controller
Comparison features&Protections | Our digital controller | Traditional controller |
Multi application in same | Application can be set | customer needs to define |
Pumps run in alternation | Yes ,pumps alternation on | in most cases it is done |
If one pump fails | Second pump starts& | Second pump doesn't start, |
Sensor less dry running | Yes | No |
Digital displaying of voltage | Yes | Mostly analogue |
Digital displaying of current | Yes | Mostly analogue |
Current overload protection | Yes | Yes |
Setting under&over voltage | Yes | No |
Displaying on faults on screen | Yes | No |
Common controller for rating from | Yes | No |
Audio alarm in case fault | Yes | No |
Setting recovery time | Yes | No |
Auto recovery from supply faults | Yes | No |
Auto/Manual Mode | Yes | Yes |
Last five faults records | Yes | No |
Run hours of each pump | Yes | No |
BMS connectivity | By default RS485 | Only in some cases with |
Products Technical Data:
Application | Control & protect sewage / drainage pump only |
Model | L932-S |
Start type | Direct on line |
Qty of controlled pump | Duplex pump |
Rated input voltage: | AC380V Three phase 50HZ/ 60HZ |
Rated output power: | 0. 75kw-4kw (1 hp-5. 5hp) 15kw (20hp) |
Protection function | Over load protection Pump stalled protection Dry run protection Under voltage protection Repeat start protection Phase unbalance protection Phase reversal protection Open phase protection |
Control characteristic | Connecting 0.5-4.5V level transmitter to replace float switch or level probe Duplex pump control ●Main pump / standby pump automatically alternate ●Main pump / standby pump automatically switch against malfunction ●Standby pump participate running if required |
Other features | LCD screen displaying dynamic real time depth & pump running status Pump shaft anti-rusty Pump accumulative running time recording Pump last five faults recording displaying Presenting one dry contact point (BA port) Present RS485 port Present user remote monitor LCD screen locked function under Auto state Push button calibration |
Working temperature Working humidity Degree of protection Install position Unit dimension (L x W x H) | -25℃-- +55℃ 20%--90%RH, no drips concreted IP54 Wall mounting 310 x 220x 1 20mm |
Tag: duplex pump control panel, duplex alternating pump controller
Hot Tags: three phase sewage water pump controller specialized in sewage lifting, China, manufacturers, suppliers, factory, price, made in China, pump controller for approvals, pump controller for optimization projects, pump controller for availability analysis, pump controller for biomass power systems, durable pump controller, pump controller for space saving